Skip navigation

Article #1468 - Residential Heating and Cooling Load Calculation Requirements - Code Notes

[2003 IRC, 2003 IECC, 2006 IECC]

It is common for mechanical systems in residential construction to be oversized which increases installation costs, wastes energy, and reduces comfort and moisture control. Properly sized equipment will last longer, provide greater comfort, reduce noise, and save homeowners money. Yet both builders and code officials are uncertain how to evaluate such calculations to assure they meet the intent of the code plus the sizing methodology approved in Air Conditioning Contractors of America (ACCA) Manual J(Link opens in a new window) (or equivalent).

The 2003 IECC requires sizing calculations to be performed on every home using the procedures described in the ASHAE Fundamentals Handbook - 2001. Chapter 14 of the 2003 IRC requires heating and cooling systems to be sized to ACCA Manual J - Seventh Addition or other approved heating and cooling load calculations. Both methods have sufficient built-in safety factors to accommodate most conditioning needs. Therefore, it is important to follow all instructions in ASHRAE Fundamentals or Manual J using precise area measurements and specific data.

Heating and cooling loads can be determined using a whole house approach or performing a room-by-room load calculation. The room-by-room approach provides the information needed to determine the number of cubic feet per minute (cfm) needed of conditioned air to satisfy the heating and cooling load for the room. This information can then be use to determine the duct size necessary to deliver space heating and cooling for the space.

The IECC regulates the outdoor design temperature for use in performing load calculations. Table 302.1 requires that the outdoor winter and summer design temperatures be based on the 97 ½ percent value for winter and 2 ½ percent value for summer based on weather data from the ASHRAE Fundamentals Handbook 2001. It is important to note that the 97 ½ percent and 2 ½ percent values have been replaced by 99.6 percent and 1.0 percent respectively in the 2001 ASHRAE Fundamentals Handbook referenced above. This reference has been changed in the 2004 version of the IECC.

There are no requirements for the indoor design temperatures for heating or cooling. ACCA recommends an indoor winter design temperature of 70 °F and a summer indoor temperature of 75 °F drybulb and 63 °F wetbulb.

To select the appropriate system based on the heating and cooling load calculations, ACCA Manual S(Link opens in a new window) should be used. Excessive oversizing equipment causes short-cycling and creates unnecessary stress on the equipment. Also larger systems require larger duct sizes which increases the installed cost. In areas where humidity is an issue, an oversized system will degrade the humidity control. A properly sized system will run almost continuously at design conditions and provide the proper level of dehumidification during the cooling season.

Plan Review:

  1. Verify that the correct outdoor design temperatures are used for the heating and cooling load calculations and that they are consistent with values in Table 302.1
  2. Verify that the building geometry and glass area match what is shown on the plans and compliance documentation. Glazing orientation is important to verify for cooling load calculations but has no effect on heat loss calculations.
  3. Verify that the levels of efficiency shown in the load calculations are consistent with the energy code compliance documentation. Insulation R-values, glazing U-factor and SHGC are important to verify.
  4. Verify that the make, model number, and equipment size is specified on the plans or compliance.

Field Inspection:

  1. Verify the make and model number for the heating and cooling system installed for the building and compare that to system specified on the building plans or documentation.
  2. If a different system is specified, verify that the system has the same output capacity and also the same level of efficiency as specified in the plans.
  3. If a larger system or an additional system is installed, require the responsible party to verify that the systems installed complies with the IECC.
  4. Verify that the efficiency levels of insulation and window efficiency (U-factors and SHGC) meet or exceed those that are called out on the plans or documentation. Levels that are too low can cause the system to be undersized. If cooling is installed, verify that the glazing area and orientation is installed per the approved building plans.
  5. Verify that the energy features of the house are installed per manufacturers installation instructions.
  6. Verify that the refrigerant charge level was tested by the installer.

Code Citations*

2003 IRC M1401.3 Sizing

Heating and cooling equipment shall be sized based on building loads calculated in accordance with ACCA Manual J or other approved heating and cooling calculation methodologies.

2003 IECC [M] 503.3.1 Load calculations.

Heating and cooling system design loads for the purpose of sizing systems and equipment shall be determined in accordance with the procedures described in the ASHRAE Fundamentals Handbook. Heating and cooling loads shall be adjusted to account for load reductions that are achieved when energy recovery systems are utilized in the HVAC system in accordance with the ASHRAE HVAC Systems and Equipment Handbook. Alternatively, design loads shall be determined by an approved equivalent computation procedure using the design parameters specified in Chapter 3.

2003 IECC Section 302 Thermal Design Parameters; 302.1 Exterior design conditions.

The following design parameters in Table 302.1 shall be used for calculations required under this code.

Table 302.1 Exterior Design Conditions

CONDITION VALUE

Winter, Design Dry-bulb (°F);

Summer, Design Dry-bulb (°F);

Summer, Design Wet-bulb (°F)

The outdoor design temperature shall be selected from the columns of 97 ½ percent values for winter and 2 ½ percent values for summer from tables in the ASHRAE Fundamentals Handbook. Adjustments shall be permitted to reflect local climates that differ from the tabulated temperatures or local weather experience determined by the code official.

Degree days heating;

Degree days cooling

The degree days heating (base 65°F) and cooling (base 65°F) shall be selected from the NOAA "Annual Degree Days to Selected Bases Derived from the 1961-1990 Normals," data available from adjacent military installations, or another source of local weather data acceptable to the code official.
Climate zone The climate zone shall be selected from the applicable map provided in Figures 902.1(1) through 902.1(51) in Chapter 9 of this code. (See Energy Code Climate Zones )

For SI: °C = [(°F)-32]/1.8

2006 IECC Section 403.6 Equipment sizing.

Heating and cooling equipment shall be sized in accordance wit hSection M1401.3 of the International Residential Code.

2006 IECC Section 302.1 Interior design conditions.

The interior design temperatures used for heating and cooling load calculations hall be a maximum of 72° (22°C) for heating and a mimimum of 75°F (24°C) for cooling.

*Copyright, 2003, International Code Council(Link opens in a new window) , Inc. Falls Church, Virginia. Reproduced with permission. All rights reserved. 2003 International Residential Code

*Copyright, 2003, International Code Council(Link opens in a new window) , Inc. Falls Church, Virginia. Reproduced with permission. All rights reserved. 2003 International Energy Conservation Code

*Copyright, 2006, International Code Council(Link opens in a new window) , Inc. Falls Church, Virginia. All rights reserved. 2006 International Energy Conservation Code .

PNNL-SA-49100
Last Modified: 2009-05-13