Article #126 - Header Hangers in Bearing Walls - Code Notes

Headers for windows and doors are typically supported by cripples or jack studs. These studs can be eliminated using header hangers, as allowed under the International Residential Code.

Eliminating unnecessary wood framing within walls can increase the thermal efficiency of the wall system. Less framing allows more insulation to be installed and also eliminates hot and cold spots (from thermal bridging through the frame) within the wall system.

Jack studs or trimmers that support headers around windows can be eliminated through the use of an approved framing anchor ("header hanger") attached to the full-height wall stud and to the header. 2000 IRC Table R502.5(1), Footnote "d" allows for the use of header hangers based on the following parameters:

Wood structural panel box headers are limited to a span of no greater than 4 feet if using a header hanger.

Plan Review

  1. Verify the number of floors and/or roof ceiling assemblies that are being supported by the header per Table R502.5(1).
  2. Verify that the building width perpendicular to the ridge is not greater than that shown in Table R502.5(1).
  3. Verify that the span of each window opening where a header hanger is proposed is not greater than the value shown in Table R502.5(1).
  4. Verify that the proposed header hanger to be used in the project has an ICC Evaluation Services report.

Field Inspection

  1. Verify that the span of the opening is not greater than that shown on the building plans.
  2. Verify that the header material is #2 grade lumber or better.
  3. Verify that the header hanger is properly nailed per the manufacturer''s instructions.

Code Citation*

IRC 2000 and 2003, Table R502.5(1) Girder Spans and Header Spans for Exterior Bearing Walls

Footnote d. NJ: Number of jack studs required to support each end. Where the number of required jack studs equals one, the headers are permitted to be supported by an approved framing anchor attached to the full-height wall stud and to the header.

*Copyright, 2000, International Code Council(Link opens in a new window) , Inc. Falls Church, Virginia. 2000 International Residential Code ; and Copyright, 2003, International Code Council(Link opens in a new window) , Inc. Falls Church, Virginia. 2003 International Residential Code . Reproduced with permission. All rights reserved.
Last Modified: 2009-05-13