Article #1467 - Whole-House Mechanical Ventilation - Code Notes
[62.2-2004, 2003 IECC, 2006 IECC]
ASHRAE Standard 62.2 provides guidance on the appropriate Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings. The information provided in the standard offers some guidance for incorporating whole-house systems into a home. This material augments requirements in the national model energy codes for compliance with mechanical ventilation systems.
At this time, the residential IECC does not reference ASHRAE 62.2.
Ventilated Mechanically
The process of supplying or removing air by mechanical means to or from any space. Such air may or may not have been conditioned.
Ventilated Naturally
The process of supplying or removing air by natural means to or from any space.
CFM
Cubic feet per minute. A standard measurement of airflow.
Historically, residential buildings did not have specific requirements for ventilation because leakage in envelope components and natural ventilation was considered adequate. As envelope construction practice has improved, the need to control air quality in the home has increased.
ASHRAE has developed a new consensus standard that provides guidelines for ventilation requirements. In addition to addressing whole-house ventilation, the standard addresses local exhaust and source control. Ventilation requirements for safety (such as garage air handlers) are also important.
To comply with the ASHRAE standard, residential buildings (including manufactured homes) are required to install a mechanical ventilation system. An override control for the occupants is also required. Ventilation systems are not currently required by the IECC in warm climates.
Plan Review:
- Confirm that a mechanical ventilation system that provides the appropriate ventilation rate (cfm) is called out.
- Check that the planned ventilation rate is not greater than 7.5 cfm per 100 square feet if located in a very cold climate or a hot-humid climate. See Table 8.1 and 8.3 for details.
- Check that other ventilation items (local exhaust) have been planned for appropriately. Typically this is simply local exhaust systems in kitchens and bathrooms.
Field Inspection:
- Confirm that a mechanical ventilation system that provides the appropriate ventilation rate (cfm) is present.
- Confirm that an occupant override has been installed as required by 62.2-2004 section 4.3 and IECC 2003 section 503.3.3.5.
Code Citations*
ASHRAE 62.2-2004, Table 4.1a (I-P) Ventilation Air Requirements, (cfm)
| Floor Area (ft²) | 0-1 bedrooms | 2-3 bedrooms | 4-5 bedrooms | 6-7 bedrooms | >7 bedrooms |
|---|---|---|---|---|---|
| <1500 | 30 | 45 | 60 | 75 | 90 |
| 1501-3000 | 45 | 60 | 75 | 90 | 105 |
| 3001-4500 | 60 | 75 | 90 | 105 | 120 |
| 4501-6000 | 75 | 90 | 105 | 120 | 135 |
| 6001-7500 | 90 | 105 | 120 | 135 | 150 |
| >7500 | 105 | 120 | 135 | 150 | 165 |
IECC 2003, Section 503.3.3.5 Mechanical ventilation.
Each mechanical ventilation system (supply, exhaust, or both) shall be equipped with a readily accessible switch or other means for shutoff (or volume reduction and shutoff) when ventilation is not required. Automatic or gravity dampers that close when the system is not operating shall be provided for outdoor air intakes and exhausts.
IECC 2006, Section 403.5 Mechanical ventilation.
Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating.
ASHRAE 62.2-2004, Table 8.1 Hot, Humid U.S. Climates
| Alabama: Mobile, Montgomery, Selma | Louisiana: Baton Rouge, Lake Charles, New Orleans, Shreveport |
| Arkansas: Texarkana | Mississippi: Biloxi, Gulfport, Jackson |
| Florida: Apalachicola, Daytona, Jacksonville, Miami, Orlando, Pensacola, Tallahassee, Tampa | North Carolina: Wilmington |
| Georgia: Savannah, Valdosta | South Carolina: Charleston, Myrtle Beach |
| Hawaii: Hilo, Honolulu, Lihue, Kahului | Texas: Austin, Beaumont, Brownsville, Corpus Christi, Dallas, Houston, Galveston, San Antonio, Waco |
ASHRAE 62.2-2004, Table 8.3 Very Cold U.S. Cities
| Alaska: Anchorage, Fairbanks | Minnesota: Duluth, International Falls |
| Maine: Caribou | North Dakota: Fargo, Grand Forks, Williston |
| Michigan: Marquette, Sault Ste. Marie |
*Copyright, 2004,
American Society of Heating, Refrigerating and Air-Conditioning Engineers
, Atlanta, GA.
ASHRAE Standard 62.2-2004
. Reproduced with permission. All rights reserved.
*Copyright, 2003,
International Code Council
, Inc. Falls Church, Virginia. Reproduced with permission. All rights reserved.
2003 International Energy Conservation Code
*Copyright, 2006,
International Code Council
, Inc. Falls Church, Virginia. All rights reserved.
2006 International Energy Conservation Code
.
